Power Settings (500 RT1U)

There are no specific settings for the Tripp-Lite Internet Office-UPS in the V1 X-Changer.  The following setup information refers only to the Tripp-Lite 500RT1U in the V2 X-Changer.

...

Legacy configuration for LaundryCard utilized a 2 min. PC shutdown timer and a 6 min. UPS shutdown timer.

Set Configuration

Frequency of Maintenance:  Review Configuration Annually

  1. Click the Windows button on the keyboard.
  2. Type Power Alert
  3. Selct PowerAlert Console when it appears (a-c is applicable to Version 7 or earlier.  For version 8 or later, skip to step 5)
    1. Open Start menu view
    2. Right-click anywhere and click ‘All apps’ at bottom/right
    3. Locate PowerAlert Console icon under the Tripp-Lite group
  4. If a Windows Security Alert dialog appears, press Allow Access
  5. From the Summary Screen, press Settings
  6. Select Device
  7. In the column next to "Low battery warning", set to:
    1. 10%
  8. Click "Apply"
  9. Click "Status"
  10. Click the Battery Icon and to the right it will show 10% next to "Low Battery Warning".
  11. Close the PowerAlert Console window.

LaundryCard Configuration


On Battery EventNot Configured
Low Battery Threshold10%
PC Shutdown Timer15 sec. after event
UPS Shutdown Timer2 min. after event

Default Configuration 

The Power Alert agent effects a shutdown of the PC and UPS after the occurrence of a Low Battery Event.  If power is restored to the UPS prior to the configured shutdown time, the device remains powered.

On Battery EventNot Configured
Low Battery Threshold50%
PC Shutdown Timer15 sec. after event
UPS Shutdown Timer2 min. after event


Testing (500 RT1U)

Frequency of Testing:  Annually

...